Troubleshooting

SMA Solar Technology AG

72

SMC70HV11-IA-IEN112970

Installation Manual

Zac-Bfr
Zac-Srr

The grid impedance has left the permissible range. The suffixes "Bfr" und
"Srr" are not relevant.
The inverter disconnects itself from the public grid for safety reasons. The
impedance is calculated from both the grid impedance and the
impedance of the AC cable of the inverter.
Corrective measures

• Check the grid impedance and grid connection on the inverter.
• Use an AC cable with an adequate cross-sectional area

(= low impedance) as described in section 5.2 "Connection to the
Power Distribution Grid (AC)" (page 24).
If required, re-tighten the
screws on the AC terminals.

• If this fault recurs, contact the SMA Serviceline.