5.2 Connection to the Power Distribution Grid (AC)

5.2.1 Conditions for the AC Connection

Cable design

Use "Sunny Design" version 2.0 or higher for the dimensioning of the conductor cross-sectional areas
(see "Sunny Design" design program at www.SMA.de/en).

Cable Requirements

Connection requirements of the distribution grid operator
Always observe the connection requirements of your distribution grid operator!

Cut line losses in half
If three inverters with symmetrical feeding are combined to form a three-phase system, the
neutral conductor is not subjected to any load, and the line losses are halved. Thus, the
maximum possible cable length is doubled.

Position

Description

Value

A

External diameter

12 mm ... 25 mm

B

Conductor cross-section

10 mm² … 16 mm²

C

Length of insulation to be stripped off

approx. 16 mm