SMA Solar Technology AG

Troubleshooting

Installation Manual

SMC70HV11-IA-IEN112970

69

Imax/overcurrent

Overcurrent on the AC side. This message is displayed if the current on
the AC grid is larger than specified.
Corrective measures

• Check the system design and grid conditions.

K1-Close
K1-Open

Fault during relay test.
Corrective measures

• If this fault frequently occurs or occurs several times consecutively,

contact the SMA Serviceline.

MSD-Fac

Internal measurement comparison fault or hardware defect.
Corrective measures

• If this disturbance occurs frequently, contact the SMA Serviceline.

MSD-Vac

Internal measurement comparison fault or hardware defect.
Corrective measures

• If this disturbance occurs frequently, contact the SMA Serviceline.

MSD-Timeout

Internal measurement comparison fault or hardware defect.
Corrective measures

• If this disturbance occurs frequently, contact the SMA Serviceline.

MSD-Zac

Internal measurement comparison fault or hardware defect.
Corrective measures

• If this disturbance occurs frequently, contact the SMA Serviceline.

Offset

The "Offset" operating state is a normal operating condition that occurs
prior to grid monitoring.
If "Offset" is displayed as a fault, then there is a disturbance in the data
logging.
Corrective measures

• If this disturbance occurs frequently, contact the SMA Serviceline.

PowerBalance

The Sunny Mini Central is part of a three-phase system with two further
Sunny Mini Centrals equipped with the SMA Power Balancer for
preventing unbalanced loads. The operation parameter "PowerBalancer"
is set to "PhaseGuard" or "FaultGuard".
Corrective measures

• For more detailed descriptions of the operation modes

"PhaseGuard" and "FaultGuard", refer to section 5.5 "Connection
of the SMA Power Balancer" (page 38).

Message

Description and corrective measure