11 technical data, Technical data – SMA SMC 7000HV Installation User Manual
Page 80

Technical Data
SMA Solar Technology AG
80
SMC70HV11-IA-IEN112970
Installation Manual
11 Technical Data
DC Input
* The maximum open-circuit voltage, which can occur at a cell temperature of − 10°C, must not exceed the maximum input voltage.
AC output
Maximum DC power at cos φ = 1
7 500 W
Maximum input voltage*
800 V
MPP voltage range
335 V … 560 V
Rated input voltage
340 V
Minimum input voltage
290 V
Start input voltage
400 V
Maximum input current
23 A
Maximum input current per string
23 A
Number of independent MPP inputs
1
Strings per MPP input
4
Rated power at 230 V, 50 Hz
6 650 W
Maximum apparent AC power
7 000 VA
Rated grid voltage
230 V
Nominal AC voltage
220 V / 230 V / 240 V
AC voltage range
180 V … 265 V
AC nominal current at 220 V
30.2 A
AC nominal current at 230 V
28.9 A
AC nominal current at 240 V
27.7 A
Maximum output current
31 A
Total harmonic factor of output current at
AC THF < 2%,
AC power > 0.5 rated power
≤ 3%
Rated power frequency
50 Hz
AC power frequency
50 Hz / 60 Hz
Operating range at AC power frequency 50 Hz
44 Hz … 55 Hz
Operating range at AC power frequency 60 Hz
54 Hz … 65 Hz
Displacement power factor, adjustable
0.8
overexcited
… 0.8
underexcited
Feed-in phases
1
Connection phases
1
Overvoltage category as per IEC 60644-1
III