SMA Solar Technology AG

Electrical Connection

Installation Manual

SMC70HV11-IA-IEN112970

39

Configuration Options

There are 4 different configuration options for the "PowerBalancer" parameter.

• FaultGuard

This operating mode allows for the implementation of a three-phase grid voltage monitoring,
which also reacts to device disturbances.
– If one of the 3 inverters indicates a grid voltage fault and stops feeding in, the other two

inverters also disconnect from the power distribution grid immediately.

– If one of the 3 inverters indicates a device fault and stops feeding in, the other two inverters

also disconnect from the power distribution grid 5 minutes later.

Local connection requirements
Select the respective setting and always observe the local connection requirements and
provisions of your distribution grid operator!