beautypg.com

SMA SMC 7000HV Installation User Manual

Page 17

background image

SMA Solar Technology AG

Mounting

Installation Manual

SMC70HV11-IA-IEN112970

17

• The connection area must point downward.
• Never mount the device with a forward tilt.
• Never install the device with a sideways tilt.
• Do not mount horizontally.
• Mount at eye level to allow operating states to be read at all times.
• The ambient temperature should be below 40°C to ensure optimum operation.
• Do not expose the inverter to direct sunlight as this can cause excessive heating and thus

power reduction.

• In living areas, do not mount the unit on plasterboard walls or similar to avoid audible

vibrations. When in use, the inverter emits noises which may be perceived as a nuisance in a
living area.

• Observe the minimum clearances to walls, other

inverters or objects as shown in the diagram in
order to ensure sufficient heat dissipation and
sufficient space for removing the
Electronic Solar Switch.

Multiple inverters installed in areas with high ambient temperatures
There must be sufficient clearance between the individual inverters to ensure that the
cooling air of the adjacent inverter is not taken in.
If necessary, increase the clearance spaces and make sure there is enough fresh air supply
to ensure sufficient cooling of the inverters.

500 mm

300 mm

300 mm

50 mm

300 mm