Electrical Connection

SMA Solar Technology AG

28

SMC70HV11-IA-IEN112970

Installation Manual

5.2.3 Additional Grounding of the Enclosure

If the installation requires, you can use the ground terminal to connect a second protective conductor
or as equipotential bonding.

Procedure

1. Insert the stripped grounding cable (D) under the

clamping clip (C) (max. cross-section 16 mm²).

2. Screw the clamping clip tight with screw (A) and

conical spring washer (B).
The toothing of the conical spring washer must face
toward the clamping clip.

☑ The inverter's enclosure is additionally grounded.