Troubleshooting

SMA Solar Technology AG

68

SMC70HV11-IA-IEN112970

Installation Manual

Derating

The "Derating" operating state is a normal operating condition which may
occur occasionally and can have several causes.
Once the inverter enters the "Derating" state, it will display the "Derating"
warning until the next total shutdown of the device (at the end of the day).
Corrective measures

• Check heat dissipation as described in section 8.2 "Checking Heat

Dissipation" (page 61).

dZac-Bfr
dZac-Srr

Sudden changes in grid impedance exceed the permissible range
("Bfr" or "Srr" are internal messages of no relevance for the user).
The inverter disconnects itself from the public grid for safety reasons.
Corrective measures
Check the grid impedance and observe how often major deviations
occur.
If repeated frequency variations occur and this is causing "dZac-Bfr" or
"dZac-Srr" errors, ask the distribution grid operator if he would agree to
modify the operation parameters (dZac-Max).
Discuss any changes to this operation parameter with the
SMA Serviceline.

EEPROM

Transition disturbance while data is being written or read from EEPROM.
The data is not relevant for safe operation.

• The disturbance has no effect on the performance of the inverter.

EEPROM dBh

EEPROM data is defective, the inverter has switched itself off because the
loss of data has disabled important functions of the inverter.
Corrective measures

• Contact the SMA Serviceline.

EeRestore

One of the duplicate data sets in the EEPROM is defective and has been
reconstructed without loss of data.

• This fault message only serves to inform you and has no effect on

the performance of the inverter.

Fac-Bfr
Fac-Srr
FacFast

The grid frequency is no longer within the permissible range
("Bfr"/"Srr"/"Fast" is an internal message that has no meaning for the
user). The inverter disconnects itself from the public grid for safety
reasons.
Corrective measures

• Check the grid connection and contact the distribution grid

operator if necessary.

• If the power frequency is within the tolerable range, but "Fac-Bfr,"

"Fac-Srr"or "FacFast" disturbances are still displayed, contact the
SMA Serviceline.

Message

Description and corrective measure