X23 Power supply at the analog inputs

Terminal Assignment

1

+24 Vdc (IEC 742 EN 50 178, 5.88 low-voltage electrical separation)

2 0

V


X19,X20,X21,X22 Connection for Pt 100 on the PL 410 B

Terminal Assignment

1

I + Constant current for Pt 100

2

U + Measuring input for Pt 100

3

U – Measuring input for Pt 100

4

I – Constant current for Pt 100

5 Shield


Connection to the analog inputs
Connecting cable 2 x 0.14 mm

2

shielded, max. 50 m.


Connection to the inputs for Pt 100 thermistors
The connection to the Pt 100 thermistors must be arranged as a four-wire circuit.
e.g. PL 410 B X19:

1

2

4

5

Measuring input U+

Measuring input U–

I+

I–

Pt100

Customer´s cable

4 x 0.14 mm

2

screened, max 50 m

3


July 02

Mounting and Electrical Installation

TNC 370 D

3–39