Mounting and Electrical Installation

July 02

3.7.8 Switching Outputs 24 Vdc for the PLC


Transistor outputs with current limiting

Logic unit

PL 410 B/PL 405 B

Min. output voltage for “1” signal

3 V below supply voltage

Nominal operating current per output

0.125 A with simultaneity
factor of 0.5

1.2 A with simultaneity
factor of 0.5;
2 A with max. current
consumption of 20 A


· Permissible load: resistive load; inductive load only with quenching diode parallel to the

inductance.

· No more than one output may be shorted on the logic unit at any time. Short circuit of one

output does not cause an overload.

· No more than half the PLC outputs may be driven at the same time (simultaneity factor 0.5).

Address

No. of outputs Device

O0 to O30

31

Logic unit X41 (PLC output)

O0 to O7

Logic unit X46 (machine operating panel)

O32 to O62

31

First PL 410 B

O64 to O94

31

Second PL 410 B

O48 to O62

15

PL 405 B


X44 Power Supply for the outputs of the LE

Terminal Assignment

PLC

outputs

1

+24 Vdc can be switched off via EMERGENCY
STOP

O0 to O23

2

+24 Vdc cannot be switched off via EMERGENCY
STOP

O24 to O30

3 0V


Power Supply for the outputs on the PL 410 B/ PL 405 B

Terminal

Assignment

1st PL 410 B
Pl 405 B

2nd PL 410 B

X9 0

V

X10

+24 Vdc power supply for logic and for control-is-ready signal

X11

+24 Vdc power supply for outputs

O32 to O39

O64 to O71

X12

+24 Vdc power supply for outputs

O40 to O47

O72 to O79

X13

+24 Vdc power supply for outputs

O48 to O55

O80 to O87

X14

+24 Vdc power supply for outputs

O56 to O62

O88 to O94


For connecting the PL 410 B to the LE, see section 3.9.14.