Mounting and Electrical Installation
TNC 370 D
3–15
3.7.6 Analog Nominal Value Output
Maximum loading of the analog outputs:
2 mA
Maximum capacitance:
2 nF
X8 Nominal Value Output
Logic unit
Connecting Cable
D-sub terminal
(female) 15-pin
Assignment D-sub
connector
(male) 15-pin
Color
1
Nominal value output 1
1
BN
2 Analog
input
2
BN/GN
3
Nominal value output 2
3
YL
4
Do not use 4
RD/BL
5
Nominal value output 3
5
PK
6
Do not use 6
GY/PK
7
Nominal value output 4
7
RD
8
Nominal value output 5
8
VI
9
0V Nominal value output 1
9
WH
10
0V Analog input
10
WH/GY
11
0V Nominal value output 2
11
GN
12
Do not use 12
13
0V Nominal value output 3
13
GY
14
0V Nominal value output 4
14
BL
15
0V Nominal value output 5
15
BK
Housing
External shield
Housing
External shield
· The connecting cables to the nominal value outputs must not have more than one intermediate
terminal.
· If it is necessary to branch to physically separate servo inputs, the connection must be
made in a grounded terminal box. Suitable terminal boxes are available from HEIDENHAIN
(Id. Nr. 251 249 01).
· The chassis of the terminal box must be electrically connected with frame of the machine.
· The 0 V connection of the nominal-value-difference inputs must be connected with signal
ground. Required cross section
³ Ø 6 mm².
· Use only original HEIDENHAIN connecting cables and connecting elements.