Technical specifications, Table e.1, Echnical – RLE LD2000 User Manual
Page 75: Pecifications

www.rletech.com
75
970.484.6510
A
P P E N D I X
C
HAPTER
0
T
ECHNICAL
S
PECIFICATIONS
Table E.1 Technical Specifications
Power
24VAC Isolated @ 600mA max, 50/60Hz; requires power
supply (not included)
24VDC@ 600mA max; requires power supply: WA-DC-24-
ST (not included)
Inputs
Water Leak Detection Cable
Compatible with SeaHawk SC Cable (not included)
Cable Input
Requires SeaHawk LC-KIT: 15ft (4.57m) leader cable and
EOL
Recommended Maximum Length
2,000ft (609m)
Detection Accuracy
± 2ft (0.6m)+/- 0.5% of the cable length
Detection Repeatability
± 2ft (0.6m) +/- 0.25% of the cable length
Detection Response Time
5-995sec, software adjustable in 5sec increments; ±2sec
Outputs
Relay
Summary Relay; 1A @ 24VDC, 0.5A resistive @ 120VAC
Communications Ports
Ethernet
10/100 BaseT, RJ45 connector; 500VAC RMS isolation
EIA-232
DB9 female connector; 9600 baud; No parity, 8 data bits,
1 stop bit
EIA-485
1200, 2400, 9600, 19200, or 38400 baud (selectable);
Parity: none, even or odd, 8 data bits, 1 stop bit