Table E.1 Technical Specifications

Power

24VAC Isolated @ 600mA max, 50/60Hz; requires power

supply (not included)
24VDC@ 600mA max; requires power supply: WA-DC-24-

ST (not included)

Inputs

Water Leak Detection Cable

Compatible with SeaHawk SC Cable (not included)

Cable Input

Requires SeaHawk LC-KIT: 15ft (4.57m) leader cable and

EOL

Recommended Maximum Length

2,000ft (609m)

Detection Accuracy

± 2ft (0.6m)+/- 0.5% of the cable length

Detection Repeatability

± 2ft (0.6m) +/- 0.25% of the cable length

Detection Response Time

5-995sec, software adjustable in 5sec increments; ±2sec

Outputs

Relay

Summary Relay; 1A @ 24VDC, 0.5A resistive @ 120VAC

Communications Ports

Ethernet

10/100 BaseT, RJ45 connector; 500VAC RMS isolation

EIA-232

DB9 female connector; 9600 baud; No parity, 8 data bits,

1 stop bit

EIA-485

1200, 2400, 9600, 19200, or 38400 baud (selectable);

Parity: none, even or odd, 8 data bits, 1 stop bit