2.1. Reset

When held this button will reset the unit and clear any alarms. The LD2000 will then recheck

for any alarm conditions.

2.2. Connections

2.2.1 TB1: Input Power

This is an optional two position connector—you may also use P1 for input power—with the

following connections:

TB1-1 24VDC positive (+)

TB1-2 24VDC negative (-)

2.2.2 P1: Input Power

This is an optional barrel connection for input power-you may also use TB1 for input power-

with the following connection:

Inside positive (+)

Outside negative (-)

Power is recommended to be supplied by a 24VDC wall adapter power supply (part

#WA-DC-24-ST), which is not included with the LD2000 and can be purchased separately.

For more information on RLE power supplies, visit the SeaHawk Accessories webpage at

www.rletech.com

, or contact RLE.

2.2.3 TB2: Cable Interface

The SeaHawk Water Leak Detection Cable (sensing cable) connects to TB2. A 15 foot

(4.57m) non-sensing leader cable is required to connect the LD2000 to the sensing cable. The

non-sensing cable is included in a leader cable kit (part #LC-KIT; purchased separately).

Connect the cable wires to TB2 as follows:

TB2-1 White wire

TB2-2 Black wire

TB2-3 Green wire

TB2-4 Red wire