10 bacnet, Bacnet, Table 4.7 – RLE LD2000 User Manual
Page 45: Bacnet configuration menu options
www.rletech.com
45
970.484.6510
4
Web Interface
Figure 4.15 Modbus/EIA-485 Configuration (Johnson N2 Shown)
4.3.10 BACnet
The BACnet Configuration page allows the user to enable the LD2000 for BACnet slave
configuration.
Table 4.7 BACnet Configuration Menu Options
BACnet
Configuration Menu
Options
Description
BACnet Device
Name
The name of the LD2000 as it will appear on the BACnet network.
BACnet Device ID
The unique identifier for the LD2000 on the BACnet network.
BACnet Description
The description of the LD2000 as it will appear on the BACnet
network.
BACnet UDP Port
The port to which the LD2000 will respond to BACnet requests. The
default number of zero in this field will configure the LD2000 to
listen on the standard BACnet port of 47808, see the BACnet
standard for more information.
BACnet MS/TP Max
Master
The highest allowable address for master nodes on the MSTP
network.
BACnet BBMD-BDT,
LD2000 IP Address,
#1 IP Address, #2 IP
Address, #3 IP
Address, #4 IP
Address
These fields give the user a reference and edit capabilities of the
BACnet Broadcast Distribution Table. These fields DO NOT need
to be configured by the user. If the LD2000 is acting as a BACnet
router, these fields will automatically be populated by the BACnet
network controller.