Installation

3.2.2 Applying Power to the LD2000

Once the SeaHawk leak detection cable (sensing cable) is connected to the unit, power can be

applied. The LD2000 operates on 24VDC or 24VAC power. A power supply is not included

with the LD2000. RLE recommends its 24VDC power supply (part #PSWA-DC-24), which

can be purchased separately. For more information on RLE power supplies, visit

www.rletech.com

, or contact RLE.

Note RLE recommends that an isolated power supply be used.

Before applying power to the unit, ensure all cable and communication connections are

complete. The LD2000 begins booting once power is applied. Wait approximately one minute.

No alarm should be present.

On the webpage interface, the cable length is displayed. If this reading varies by more than

±5% of the actual length of cable installed, verify the installation. The LD2000 should not

require any calibration. If any calibration is required, verify that the cable current is zero

before calibrating or false, inaccurate readings will occur.

Through the webpage submenus, you may set the clock, system name, alarm configuration,

feet/meters, etc.