beautypg.com

B.3. configuring the ld2000 modbus communications, Configuring the ld2000 modbus communications, Figure b.4 zone configuration – RLE LD2000 User Manual

Page 67

background image

www.rletech.com

67

970.484.6510

B

Leak Detection Modbus Master

B.3.

Configuring the LD2000 Modbus

Communications

Log into the LD2000 web interface and configure the unit to be a Modbus master:

1

From the Home page, click the Configuration link in the top bar. If using the EIA-485 port,

click on EIA-485 Port/Modbus/N2.

2

Once on the Modbus/EIA-485 Configuration page, select Modbus-Master or N2 from the

Select EIA-485 Port Function drop down. When completed, click on the submit changes

tab.

Figure B.3 Modbus/EIA-485 Configuration (Johnson N2 Shown)

Next, configure the slave units:

3

From the LD2000 Home page, click the Configuration link in the top bar. Choose from the

following options based on the configuration you want to set up:

a

To use addresses 2 through 8, choose

Zone Settings???

.

b

If using zones 1-8 for virtual zone labeling, use

Zone 9-16 Settings //what is this called

now?//

.

c

If you are not using the virtual zone feature, check the

Physical-Modbus/485

option.

Trap notifications can be enabled or disabled on individual units via the Modbus/EIA-

485 Configuration page. Click the submit changes button to save changes. Return to the

Configuration screen when finished.

Figure B.4 Zone Configuration