Table 5.6, Status flags (register 30001), Table 5.7 – RLE LD2000 User Manual
Page 56: Status flags (register 30010), Table 5.8, Status flags (register 30011)
www.rletech.com
56
970.484.6510
5
Modbus Communication
Table 5.6 Status Flags (Register 30001)
Bit
Description
00
1 = Leak is Detected
01
1 = Cable Break Alarm
02
1 = Contamination is detected
04-15
Spare
Table 5.7 Status Flags (Register 30010)
Bit
Description
00
1 = Zone1
01
1 = Zone2
02
1 = Zone3
03
1 = Zone4
04
1 = Zone5
05
1 = Zone6
06
1 = Zone7
07
1 = Zone8
Table 5.8 Status Flags (Register 30011)
Bit
Description
00
1 = Not enabled
01
1 = Enabled, b1=MBZ2
02
1 = MBZ3
03
1 = MBZ4
04
1 = MBZ5
05
1 = MBZ6
06
1 = MBZ7
07
1 = MBZ8
08
1 = MBZ9
09
1 = MBZ20
10
1 = MBZ11
11
1 = MBZ12
12
1 = MBZ13
13
1 = MBZ14