Figure b.2 address assignment for units – RLE LD2000 User Manual
Page 66

www.rletech.com
66
970.484.6510
B
Leak Detection Modbus Master
B.2.
Connecting Distance Read Panels to the LD2000
(Ethernet)
When using the LD2000 as a Modbus master, the slave unit(s) can be connected to the
LD2000 by using the local network connection, TCP/IP or UDP/IP. You will have to set the
TCP/IP, UDP/IP slave address in each Leak detection unit(s) with distance read panels that
have an Ethernet port. The first unit connected must be set to address 2 or higher. The
following units will increase in numeric order by one unit (e.g., the next unit would be set to
address 3, the following would be set to address 4, etc.; see Figure B-2.)
Set the TCP/IP, UDP/IP slave address for every distance read modules connected via the
Ethernet. The Modbus communications uses port #502 for the IP address assigned.
Figure B.2 Address Assignment for Units