beautypg.com

Modbus communication, Implementation basics, 1 modes of transmission – RLE LD2000 User Manual

Page 51: 1 slave address field, Modes of transmission, Slave address field, Odbus, Ommunication

background image

www.rletech.com

51

970.484.6510

C

H A P T E R

C

HAPTER

4

M

ODBUS

C

OMMUNICATION

This chapter describes the Modbus communication protocol as supported by the LD2000

Distance Read System. The content includes details and information on how to configure the

LD2000 for communications via Modbus network

5.1. Implementation

Basics

The LD2000 is capable of communicating via the half-duplex EIA-485 serial communication

standard. The LD2000 is configured to act as a slave device on a common network. The EIA-

485 medium allows for multiple devices on a multi-drop network. The LD2000 is a slave only

device and will never initiate a communications sequence.

5.1.1 Modes of Transmission

The Modbus protocol uses ASCII and RTU modes of transmission. The LD2000 supports only

the RTU mode of transmission, with 8 data bits, no parity and one stop bit. Every Modbus

packet consists of four fields:



Slave Address Field



Function Field



Data Field



Error Check Field (Checksum)

5.1.1.1 Slave

Address

Field

The slave address field is one byte in length and identifies the slave device involved in the

transaction. A valid address range is between 1 and 254. The slave address is set from the

Modbus/EIA-485 Configuration webpage (see 4.3.9, “Modbus” on page 43).