beautypg.com

1 securing cable to the floor, Securing cable to the floor, Figure 3.2 cable installation methods – RLE LD2000 User Manual

Page 22

background image

www.rletech.com

22

970.484.6510

3

Installation

4

Route the sensing cable according to a cable layout diagram, if provided.

5

Secure the EOL terminator on the unoccupied end of the sensing cable.

3.2.1 Securing Cable to the Floor

Secure the sensing cable to the floor with either J-clips (part #JC), or one of the other approved

methods shown in Figure 3.2. Available from RLE and designed specifically for use with

sensing cable, J-clips (part #JC) are the manufacturer's recommended installation method and

can be installed as follows:



Place one J-clip every 5 to 6 feet (1.52 to 1.83m) along the length of the sensing cable and

one at each turn of the cable. Use more J-clips if a “tighter” configuration is required.



If the cable is installed over an obstruction, clip the cable on both sides, as close to the

obstruction as possible.

Do not install the cable directly in front of an air conditioner. Allow a minimum of 4

to 6 feet (1.22 to 1.83m) between the unit and the cable. If the cable is too close to

the air conditioning unit’s air stream, the moisture from the humidifier may cause

false leak readings. If the cable must be installed in front of an air conditioning

unit, place the J-clips 12 to 18 inches (.305 to .457m) apart.



Finish the end of the SeaHawk leak detection cable (sensing cable) with the end terminator

(EOL) that is shipped with the LD2000. If the EOL terminator is not present, a cable fault

will register. Note any variances between the cable layout diagram and the actual cable

installation.

Figure 3.2 Cable Installation Methods

W

ARNING