2 technical data, 1 unit data, Technical data 2.1 unit data – REMKO HTS 90 ALU User Manual
Page 9: 2technical data
2
Technical data
2.1 Unit data
HTS 90 / HTS 130
Series
HTS 90
HTS 130
Function
Heating or Cooling
System
Split-Air/Water
Heat pump manager
Smart Control
Inlet temperature for heating water, max. (up to -7°C)
°C
63
Min. inlet temperature for cooling
°C
7
Number of outdoor units
1
1
Electrical booster heating / rated output
kW
optional / 9.0
Drinking water heating (changeover valve)
optional outdoor
Connection oil / gas boiler
optional outdoor
Rated output min. / max.
kW
2.5 - 13.0
Rated output / revolutions rps / COP
1)
at A12/W35
kW/Hz/COP
7.90/56/5.68
10.82/56/5.42
Rated output / revolutions rps / COP
1)
at A7/W35
kW/Hz/COP
7.29/56/5.09
10.31/56/4.95
Rated output / revolutions rps / COP
1)
at A2/W35
kW/Hz/COP
5.26/56/3.77
7.41/56/3.71
Rated output / revolutions rps / COP
1)
at A-7/W35
kW/Hz/COP
4.84/56/3.17
6.76/56/3.27
Rated output / revolutions rps / COP
1)
at A-15/W35
kW/Hz/COP
4.20/60/2.89
6.26/62/2.75
Rated output / revolutions rps / COP
1)
at A-20/W35
kW/Hz/COP
3.56/60/2.42
5.44/62/2.16
Rated output / revolutions rps / COP
1)
at A7/W45
kW/Hz/COP
7.01/56/3.92
9.75/56/3.77
Rated output / revolutions rps / COP
1)
at A-7/W45
kW/Hz/COP
5.05/56/2.80
7.11/62/2.53
Rated output / revolutions rps / COP
1)
at A7/W55
kW/Hz/COP
6.54/56/3.04
9.23/62/2.94
Rated output / revolutions rps / COP
1)
at A-7/W55
kW/Hz/COP
5.28/60/2.46
6.47/56/2.09
Cooling performance min. / max.
kW
1.2-8.0
2.3 - 11.0
Cooling performance / revolutions rps / EER
2)
at A35/W7
kW/Hz/EER
5.45/58/2.35
7.77/58/2.28
Cooling performance / revolutions rps / EER
2)
at A35/W18
kW/Hz/EER
5.52/40/3.45
7.85/40/3.37
Cooling performance / revolutions rps / EER
2)
at A27/W18
kW/Hz/EER
5.41/40/3.52
7.57/40/3.39
9