beautypg.com

Fig. 17), Fig. 18), Remko hts – REMKO HTS 90 ALU User Manual

Page 38

background image

20 cm

1

Fig. 17: Protection against snow

1: Snow

1

2

2

1

Fig. 18: Air intake and air outlet on outdoor module

1: Air intake

2: Air outlet

Point of emissions

Assessment level in accordance

with TA noise

daytime in

dB(A)

night-time in

dB(A)

Industrial areas

70

70

Commercial areas

65

50

Core areas, village areas and mixed zones

60

45

General residential areas and small housing estates

55

40

Exclusively residential areas

50

35

Spa areas, hospitals and mental institutions

45

35

Isolated noise peaks of short duration may not exceed 30 dB(A) during the day and 20 dB(A) at night.

Definition of the Danger Area

WARNING!

Access to the unit is only permitted for author-

ised and trained persons. If unauthorised per-

sons can approach the danger areas, these

areas must be identified with corresponding

signs, barriers, etc.

n

The external danger area surrounds the equip-

ment up to a distance of 2 m, measured in all

directions from the unit housing.

n

The external danger area on-site can differ as

a result of the set-up. The specialist company

performing the installation work bears the

responsibility for this.

n

The internal danger area is located inside the

machine and can only be reached with the use

of an appropriate tool. Access is prohibited for

unauthorised persons!

REMKO HTS

38