20 cm
1
Fig. 17: Protection against snow
1: Snow
1
2
2
1
Fig. 18: Air intake and air outlet on outdoor module
1: Air intake
2: Air outlet
Point of emissions
Assessment level in accordance
with TA noise
daytime in
dB(A)
night-time in
dB(A)
Industrial areas
70
70
Commercial areas
65
50
Core areas, village areas and mixed zones
60
45
General residential areas and small housing estates
55
40
Exclusively residential areas
50
35
Spa areas, hospitals and mental institutions
45
35
Isolated noise peaks of short duration may not exceed 30 dB(A) during the day and 20 dB(A) at night.
Definition of the Danger Area
WARNING!
Access to the unit is only permitted for author-
ised and trained persons. If unauthorised per-
sons can approach the danger areas, these
areas must be identified with corresponding
signs, barriers, etc.
n
The external danger area surrounds the equip-
ment up to a distance of 2 m, measured in all
directions from the unit housing.
n
The external danger area on-site can differ as
a result of the set-up. The specialist company
performing the installation work bears the
responsibility for this.
n
The internal danger area is located inside the
machine and can only be reached with the use
of an appropriate tool. Access is prohibited for
unauthorised persons!
REMKO HTS