Remko hts – REMKO HTS 90 ALU User Manual
Page 60

Error
ID
Description
Desig
.
Details
ID7050 Anti-freeze protection
The anti-freeze protection in the heat pump's heat exchanger
was triggered due to an inlet temperature of less than the min-
imum temperature. After eliminating the cause of the error, the
controller must be restarted to reset the error
ID7150 EEV motor fault
EEV motor fault. Please contact an authorised service techni-
cian
ID7200 Open contact - storage
tank 1 bottom probe
S02
Open contact - storage tank 1 bottom probe
ID7201 Short circuit - storage
tank 1 bottom probe
S02
Short circuit - storage tank 1 bottom probe
ID7202 Open contact - storage
tank 1 middle probe
S09
Open contact - storage tank 1 middle probe
ID7203 Short circuit - storage
tank 1 middle probe
S09
Short circuit - storage tank 1 middle probe
ID7204 Open contact - storage
tank 1 top probe
S08
Open contact - storage tank 1 top probe
ID7205 Short circuit - storage
tank 1 top probe
S08
Short circuit - storage tank 1 top probe
ID7206 Open contact - external
probe
S10
Open contact - external probe
ID7207 Short circuit -
external probe
S10
Short circuit - external probe
ID7208 Open contact -
refrigerant probe
S07
Open contact - refrigerant probe
ID7209 Short circuit - refrig-
erant probe
S07
Short circuit - refrigerant probe
ID7210 Open contact - circula-
tion temp. probe
S05
Open contact - drinking water circulation temperature probe
ID7211 Short circuit - circula-
tion temp. probe
S05
Short circuit - drinking water circulation temperature probe
ID7212 Open contact - inlet
temp. probe
S13
Open contact - inlet temp. probe
ID7213 Short circuit - inlet
temp. probe
S13
Short circuit - inlet temp. probe
ID7218 Open contact - collector
1 probe
S01
Open contact - collector 1 probe
ID7219 Short circuit -
collector 1 probe
S01
Short circuit - collector 1 probe
ID7228 Open contact - inlet
temp. probe
S13.2 Open contact - inlet temp. probe
ID7229 Short circuit - inlet
temp. probe
S13.2 Short circuit - inlet temp. probe
REMKO HTS