beautypg.com

5 hydraulic connection, Hydraulic connection, 5hydraulic connection – REMKO HTS 90 ALU User Manual

Page 41

background image

5

Hydraulic connection

A separate interpretation of nominal flow rate

must be made for every system (see technical

data).

n

We recommend installing a buffer storage unit

as a hydraulic switch for hydraulic isolation of

the heating circuit.
Hydraulic isolation is required when:
- different inlet temperatures need to be ach-

ieved, e.g. underfloor heating / radiators
- the pressure drop in the heating distribution

system is greater than 80 kPa
- the use of other heat sources, e.g. solid fuel

boiler, solar or bivalent (duel-fuel) systems

n

Make a pipe-network calculation before instal-

ling the heat pump. After installing the heat

pump, it is necessary to perform a hydraulic

balancing of the heating circuit.

n

Protect underfloor heating systems against

excessively high inlet temperatures.

n

Do not reduce pipe diameters for the supply

and return connections to the heat pump

before connecting a buffer storage-unit.

n

Plan for air bleed valves and drain-off taps at

appropriate places.

n

Flush the system's entire pipe network before

connecting the heat pump.

n

One or, where necessary, several expansion

tanks must be designed for the entire hydraulic

system.

n

The system pressure of the entire pipe network

is to be matched to the hydraulic system and

must be checked when the heat pump is

turned off. Also update the static-pressure form

supplied with the heat pump.

n

As delivered, the safety assembly consists of a

pressure gauge, an air bleeder and a safety

valve. It must be mounted on a tee between

heat pump adapter and delivered stopcock.
The supplied shut-off valves are to be set

directly behind the safety assembly in the

heating circuit flow and return (Fig. 24). The

shut-off valves each contain a thermometer.

Fig. 23: Shut-off valves

Turning the thermometer heads serves to close

or open the stop valves! The dial be brought

into the desired position.

n

Install the dirt trap delivered with the unit out-

side the heat pump in the return line. Ensure

that the dirt trap remains accessible for inspec-

tion.

n

Be sure to position one gate valve upstream

and another downstream of the dirt trap. This

ensures that the dirt trap can be checked at

any time without loosing water.

n

The dirt trap must be checked during every

service of the system.

n

Additionally, a hand-operated bleeder is

installed on the heat pump for additional

bleeding.

n

All visible metallic surfaces must be addition-

ally insulated.

n

Cooling mode via the heating circuit requires a

completely vapour diffusion tight insulation

along the entire length of the pipework.

n

All outgoing heating circuits, including the con-

nections for water heating, are to be secured

against circulating water by means of check

valves.

n

Before being placed in service, the system

must be thoroughly flushed. Conduct a seal

test and perform a thorough bleeding of both

the indoor module and the entire system -

repeatedly, if necessary, in acc. with DIN

standards.

n

To prevent structure-borne transmission, we

advise you to install additional compensators in

the inlet and return lines.

Actual schemas for hydraulic integration can

be found on the internet at www.remko.de

41