beautypg.com

Remko hts – REMKO HTS 90 ALU User Manual

Page 30

background image

Heat pump operating mode

Heat pumps can work in various operating modes.

Monovalent

The heat pump the only source of heat for a

building all year round. This mode is particularly

suitable for heating plants with low supply-water

temperatures and is primarily used in combination

with brine/water and water/water heat pumps.

Monoenergetic

The heat pump has an E-heater to handle peak

loads. The heat pump covers the majority of the

required heating power. Occasionally, when it is

extremely cold outside, an electrical booster-

heating system switches on as required in order to

support the heat pump.

Bivalent alternative

The heat pump provides the entire heating energy

down to a predetermined outdoor temperature. If

the ambient temperature drops below this value, a

second heat source switches on to support the

heat pump, which shuts down at this point. At this

point, a distinction is made between alternative

operation with oil or gas heating and regenera-

tive operation with solar energy or wood heating.

This operating mode is possible for all heating sys-

tems.

Layout

A precise calculation of the building's heating load

according to EN 12831 is required for the design

and dimensioning of a heating system. However,

approximate requirements can be determined

based on the year of construction and the type of

building. This table

Ä on page 31 provides an

approximate specific heating load for a few types

of building. The required heating system output

can be calculated by multiplying the area to be

heated with the given values.

For a precise calculation, various factors must be

considered. The transmission-heat requirement,

the infiltration heat-loss and an allowance for water

heating comprise the total heating output which the

heating system must provide.

The total area of the floor surfaces, exterior wall

windows, doors and roofing is required in order to

determine the transmission heat requirement. In

addition, information about the materials used in

the building is required, as well as about the dif-

ferent thermal transmission coefficients (known as

the K value). Also required are the room tempera-

ture and the standard outdoor temperature, that is,

the lowest outdoor-temperature on average that

will occur during the year. The equation for deter-

mining the thermal transmission requirement is

Q=A x U x (t

R

-t

A

) and must be calculated for all

enclosed room floor areas.

The infiltration heat requirement takes into consid-

eration how often the heated room air is

exchanged for cold external air. The room volume

(V), the air exchange frequency (n) and the spe-

cific heat capacity (c) of the air is also required in

addition to the room temperature and average low

temperature. The equation is: Q=V x n x c (t

R

-t

A

)

An approximate addition for the preparation of

domestic water per person amounts in acc. with

VDI 2067: 0.2 kW.

Design example

By way of a design example, a residential home

with a living area of 150 m² and a heating require-

ment of approx. 80 W/m² was selected. A total of

five persons live in the house. The heat load

amount to 11.5 kW. Adding a drinking water allow-

ance of 0.2 kW results in a required heat output of

12.5 kW. Depending on the power company, an

additional charge must then be made in order to

factor in any service time-out periods that may

apply. The rating and determination of the heat

pump's balance-point temperature derives graphi-

cally from the heat pump's inlet temperature-speci-

fication heat-output diagram (in this example 35°C

for underfloor heating). Next, the heat load for the

standard outdoor temperature (the lowest tempera-

ture of the year locally) and the heat threshold are

marked on the graph. The outdoor-temperature-

dependent heating requirement, (Fig. 9) simplified

here as a straight-line relationship between heat-

load and the start of the heating season, is

recorded in the graph of heat-load curves. The

intersection of the two straight lines with the rated

heat-load curve is plotted on the X axis, where the

balance-point temperature is read (in this example

approx. -3°C). The minimum performance of the

2nd heat source is the difference between heat

load and the heat pump's maximum heat output on

these days (in this example, the required power

required to cover peak load requirements is

approx. 3 kW).

REMKO HTS

30