beautypg.com

2 commissioning the refrigeration system, Remko hts, 2 commissioning the refrigera- tion system – REMKO HTS 90 ALU User Manual

Page 52

background image

2

1

Fig. 33: Deburring the refrigerant piping

1: Refrigerant piping

2: Deburrer

Connection to the unit

n

Take off the factory-fitted protective caps.

n

The connection of the refrigerant pipes to the

device connections are to initially be made by

hand, in order to ensure a good fit. Then the

connection is brazed.

n

The installed refrigerant pipes must be pro-

vided with suitable insulation.

n

Special measures need not be taken for the

return of the compressor oil.

NOTICE!

Use only tools which are approved for use in

an HVAC environment. (z. B.: bending pliers,

pipe/tubing cutters, de-burrers and flaring

tools). Do not cut refrigerant pipes with a saw.

NOTICE!

All work must be carried out in a way that pre-

vents dirt, particles, water etc. from entering,

refrigerant lines!

NOTICE!

Soldering is only permitted in an inert gas

atmosphere!

9.2 Commissioning the refrigera-

tion system

Leak testing

Once all the connections have been made, the

pressure gauge station is attached to the Schrader

valve as follows (if fitted):

blue = large valve = suction pressure

Once the connection has been made successfully,

the leak test is carried out with dry nitrogen. Leak

testing involves spraying a leak detection spray

onto the connections. If bubbles are visible, the

connections have not been made properly. Then

produce a soldered connection.

Pumping down to vacuum

After completing a successful leak test, the excess

pressure in the refrigerant piping is removed and a

vacuum pump with an absolute final partial pres-

sure of min. 10 mbar is used to remove all of the

air and empty the pipes. Any moisture present in

the pipes will also be removed.

The connections can be found on the indoor

module above the shut-off valves.

NOTICE!

A vacuum of at least 10 mbar must be pro-

duced!

The time required to generate the vacuum is

dependent on the final pressure pipe volume of the

indoor units and the length of the refrigerant pipes.

This always takes at least 60 minutes. Once any

foreign gases and humidity have been completely

extracted from the system, the valves on the pres-

sure gauge station are closed and the valves on

the outdoor unit are opened as described in the

"Commissioning" section.

REMKO HTS

52