4.3 Layout, assembly

indoor module

n

Depending on local conditions, the noise emis-

sion level of the indoor unit should be taken

into account, and where necessary acoustic

insulation measures should be adopted.

n

Ensure that the wall bracket is installed level.

n

The indoor module can be aligned precisely by

means of the adjustment screws on the back of

the housing.

n

The indoor module is to be mounted in such a

way that all of the sides have sufficient space

for purposes of installation and maintenance. It

is equally important that there is sufficient

space above the device for installing the safety

assembly, dirt traps etc.

Fig. 15: Layout, indoor module

Minimum spacing for indoor module

1000

300

300

Fig. 16: Recommended minimum spacing for

indoor module (figures in mm)

4.4 Layout, assembly of

outdoor module

Outdoor module installation location

n

The device may be attached only to a load-

bearing structure or wall. Ensure that the out-

door module is installed only vertically. The

installation site should be well ventilated.

n

To minimise noise, install floor consoles with

vibration dampers and a considerable distance

from acoustically-reflective walls to minimise

noise.

n

The minimum clearances specified on the next

page should be maintained when carrying out

the installation. These minimum distances

serve to ensure unrestricted air intake and

exhaust. Additionally, there must be adequate

space available for installation, maintenance

and repair.

n

If the outdoor module is erected in an area of

strong winds, then the device must be pro-

tected against them and it is recommended an

additional stabilization. This can, for example,

be realized with ropes or other structures. The

snow line is to be observed during installation

(Fig. 17).

n

A heated, condensate catch-pan ensures that

condensation from the pan can drain off.

Ensure that the condensate is prevented from

freezing so that it can drain off (gravel,

drainage). The Water Ecology Act is to be

observed (Fig. 21).

n

During installation, add about 20 cm to the

expected snow depth to guarantee unimpeded

intake and exhaust of outdoor air year round

(Fig. 17).

n

The installation site of the outdoor module

should be agreed together with the operator

primarily so that 'non-concerning levels of

operating noise' are achieved, rather than in

respect of 'short distances'. This is because:

Thanks for splitter technology, there is a vast

amount of different installation options with

almost identical efficiency available.

n

Air suction takes place in the bottom area of

the plate heat exchanger. Air outflow takes

place upwards in a perpendicular direction

(Fig. 18).

NOTICE!

The site for the outdoor unit must be selected

so that machinery noise that occurs disturbs

neither the residents nor the facility operator.

Observe the TA-noise specifications as well as

the table containing the drawings relating to

sound pressure levels.