HTS 200 / HTS 260

Series

HTS 200

HTS 260

Function

Heating or Cooling

System

Split-Air/Water

Heat pump manager

Smart Control

Inlet temperature, heating water, max.

°C

63

Min. inlet temperature for cooling

°C

7

Number of outdoor units

2

2

Electrical booster heating / rated output

kW

optional / 9.0

Drinking water heating (changeover valve)

optional outdoor

Connection oil / gas boiler

optional outdoor

Rated output min. / max.

kW

3.0 - 18.0

5.0 - 26.0

Rated output / revolutions rps / COP

1)

at A12/W35

kW/Hz/COP

16.12/56/5.65

21.63/56/5.40

Rated output / revolutions rps / COP

1)

at A7/W35

kW/Hz/COP

15.51/60/5.01

20.62/55/4.98

Rated output / revolutions rps / COP

1)

at A2/W35

kW/Hz/COP

12.00/60/3.91

17.41/54/3.82

Rated output / revolutions rps / COP

1)

at A-7/W35

kW/Hz/COP

9.64/60/3.43

13.55/54/3.24

Rated output / revolutions rps / COP

1)

at A-15/W35

kW/Hz/COP

8.62/60/2.98

12.52/62/2.76

Rated output / revolutions rps / COP

1)

at A-20/W35

kW/Hz/COP

7.94/60/2.41

10.83/62/2.19

Rated output / revolutions rps / COP

1)

at A7/W45

kW/Hz/COP

14.20/60/3.89

19.87/54/3.79

Rated output / revolutions rps / COP

1)

at A-7/W45

kW/Hz/COP

9.06/60/2.71

13.58/58/2.50

Rated output / revolutions rps / COP

1)

at A7/W55

kW/Hz/COP

13.15/60/3.15

18.47/54/2.95

Rated output / revolutions rps / COP

1)

at A-7/W55

kW/Hz/COP

8.51/62/2.25

11.64/54/2.01

Cooling performance min. / max.

kW

3.4 - 14.8

4.4 - 19.0

Cooling performance / revolutions rps / EER

2)

at A35/W7

kW/Hz/EER

10.40/54/2.37

14.82/54/2.48

Cooling performance / revolutions rps / EER

2)

at A35/W18

kW/Hz/EER

12.4/40/3.51

16.10/40/3.66

Cooling performance / revolutions rps / EER

2)

at A27/W18

kW/Hz/EER

11.8/41/3.66

15.77/40/3.82

REMKO HTS