HTS 200 / HTS 260
Series
HTS 200
HTS 260
Function
Heating or Cooling
System
Split-Air/Water
Heat pump manager
Smart Control
Inlet temperature, heating water, max.
°C
63
Min. inlet temperature for cooling
°C
7
Number of outdoor units
2
2
Electrical booster heating / rated output
kW
optional / 9.0
Drinking water heating (changeover valve)
optional outdoor
Connection oil / gas boiler
optional outdoor
Rated output min. / max.
kW
3.0 - 18.0
5.0 - 26.0
Rated output / revolutions rps / COP
1)
at A12/W35
kW/Hz/COP
16.12/56/5.65
21.63/56/5.40
Rated output / revolutions rps / COP
1)
at A7/W35
kW/Hz/COP
15.51/60/5.01
20.62/55/4.98
Rated output / revolutions rps / COP
1)
at A2/W35
kW/Hz/COP
12.00/60/3.91
17.41/54/3.82
Rated output / revolutions rps / COP
1)
at A-7/W35
kW/Hz/COP
9.64/60/3.43
13.55/54/3.24
Rated output / revolutions rps / COP
1)
at A-15/W35
kW/Hz/COP
8.62/60/2.98
12.52/62/2.76
Rated output / revolutions rps / COP
1)
at A-20/W35
kW/Hz/COP
7.94/60/2.41
10.83/62/2.19
Rated output / revolutions rps / COP
1)
at A7/W45
kW/Hz/COP
14.20/60/3.89
19.87/54/3.79
Rated output / revolutions rps / COP
1)
at A-7/W45
kW/Hz/COP
9.06/60/2.71
13.58/58/2.50
Rated output / revolutions rps / COP
1)
at A7/W55
kW/Hz/COP
13.15/60/3.15
18.47/54/2.95
Rated output / revolutions rps / COP
1)
at A-7/W55
kW/Hz/COP
8.51/62/2.25
11.64/54/2.01
Cooling performance min. / max.
kW
3.4 - 14.8
4.4 - 19.0
Cooling performance / revolutions rps / EER
2)
at A35/W7
kW/Hz/EER
10.40/54/2.37
14.82/54/2.48
Cooling performance / revolutions rps / EER
2)
at A35/W18
kW/Hz/EER
12.4/40/3.51
16.10/40/3.66
Cooling performance / revolutions rps / EER
2)
at A27/W18
kW/Hz/EER
11.8/41/3.66
15.77/40/3.82
REMKO HTS