beautypg.com

Remko hts – REMKO HTS 90 ALU User Manual

Page 54

background image

CAUTION!

Danger of injury from refrigerant!

Refrigerant degreases the skin on contact and

may cause cold burns.

Therefore:

- Wear chemical-resistant protective gloves

when undertaking any work involving refriger-

ants.

-Safety glasses must be worn to protect the

eyes.

n

The indoor module is pre-filled with refrigerant

sufficient for a length of ordinary pipe up to

7 metres.

n

If the length of any of the pipelines exceeds

7 metres, then an additional filling is required

for each additional metre of pipe length to the

outdoor module (basic length).

Basic pipe length

per outdoor module

Additional fill quantity

per outdoor module

Up to and incl. 7 m

0 g/m

From 7 m

per outdoor module

30 g/m

Examples

Basic pipe length

per outdoor module

Additional fill quantity

per outdoor module

7 m

0 g

10 m

90 g

15 m

240 g

20 m

390 g

25 m

540 g

30 m

(only HTS 90/130)

690

50 m

(only HTS 90/130)

1,290 g

NOTICE!

The escape of refrigerant contributes to cli-

matic change. In the event of escape, refrig-

erant with a low greenhouse potential has a

lesser impact on global warming than those

with a high greenhouse potential. This device

contains refrigerant with a greenhouse poten-

tial of 1975. That means the escape of 1 kg of

this refrigerant has an effect on global warming
that is 1975 times greater than 1 kg CO

2

,

based on 100 years. Do not conduct any work

on the refrigerant circuit or dismantle the

device - always enlist the help of qualified

experts.

REMKO HTS