Remko hts – REMKO HTS 90 ALU User Manual
Page 54

CAUTION!
Danger of injury from refrigerant!
Refrigerant degreases the skin on contact and
may cause cold burns.
Therefore:
- Wear chemical-resistant protective gloves
when undertaking any work involving refriger-
ants.
-Safety glasses must be worn to protect the
eyes.
n
The indoor module is pre-filled with refrigerant
sufficient for a length of ordinary pipe up to
7 metres.
n
If the length of any of the pipelines exceeds
7 metres, then an additional filling is required
for each additional metre of pipe length to the
outdoor module (basic length).
Basic pipe length
per outdoor module
Additional fill quantity
per outdoor module
Up to and incl. 7 m
0 g/m
From 7 m
per outdoor module
30 g/m
Examples
Basic pipe length
per outdoor module
Additional fill quantity
per outdoor module
7 m
0 g
10 m
90 g
15 m
240 g
20 m
390 g
25 m
540 g
30 m
(only HTS 90/130)
690
50 m
(only HTS 90/130)
1,290 g
NOTICE!
The escape of refrigerant contributes to cli-
matic change. In the event of escape, refrig-
erant with a low greenhouse potential has a
lesser impact on global warming than those
with a high greenhouse potential. This device
contains refrigerant with a greenhouse poten-
tial of 1975. That means the escape of 1 kg of
this refrigerant has an effect on global warming
that is 1975 times greater than 1 kg CO
2
,
based on 100 years. Do not conduct any work
on the refrigerant circuit or dismantle the
device - always enlist the help of qualified
experts.
REMKO HTS