Remko hts – REMKO HTS 90 ALU User Manual
Page 10
Series
HTS 90
HTS 130
Usable limits, heating
°C
-20 - +45
Service limits, cooling
°C
+15 - +45
Refrigerant / pre-charge quantity indoor module
-- / kg
R 410A
2)
/
1.75
R 410A
2)
/
2.95
Refrigerant / pre-charge quantity
for more than 7 m length of ordinary pipe
g / m
30
Refrigerant connections on outdoor module
Inches (mm)
3/8" (9.52) / 5/8" (15.9)
Refrigerant connections on indoor module
Inches (mm)
3/8" (9.52) / 5/8" (15.9)
Refrigerant piping length, total
(simple length)
m
30
50
Refrigerant piping height, max.
m
10
30
Power supply indoor module
V / Ph / Hz
230V /1 Ph/
50Hz
400V /3 Ph/
50Hz
Power supply to indoor module control unit
V / Ph / Hz
230V /1 Ph/50Hz
Power supply to electrical heating coil
V / Ph / Hz
400V /3 Ph/ 50Hz
Max. current consumption
A
12.2
7.3
Rated current consumption for A7/W35
A
6.5
4.08
Rated power consumption for A7/W35
kW
1.43
2.08
Rated power consumption for A2/W35
kW
1,49
1,99
Max. power consumption
kW
2.52
4.21
Power factor at A7/W35 (cosφ)
--
0.9
0.8
Customer's fuse protection indoor module
A slow-
acting
16
3 x 16
Rated water flow (according to EN 14511, at ∆t 5 K)
m³/hr
1.25
1.79
Pressure loss on condenser at rated volumetric flow rate
bar
0.17
0.25
Pressure loss, outdoor
kPa
80
Airflow volume outdoor module
m³/hr
2700
Max. operating pressure, water
bar
3
Hydraulic connection inlet/return flow, flat-sealing
Inches
1"
Recommended pipe dimension Cu copper
mm
28
Water volume, indoor module
l
4.2
4,8
Refrigerant oil
Type
Synthetic Oil FV50S
Rated power intake of indoor module pump, min./max.
W
7 / 136
Rated input power of each outdoor module fan
W
125
125
Rated power intake of indoor module pump, min./max.
A
0.07 / 1.03
Volumetric flow rate of indoor module pump, min./max.
m³/hr
0.9/2.0
0.9/2.0
Motor protection, indoor module pump
--
Resistant to blocking current
REMKO HTS
10