14.2 Error messages on the Smart-Control

Operating messages, warnings and error display on the Smart-Control

Operating messages

ID

Description

Desig

.

Details

ID6000 Storage tank 1: Max.

temperature reached

The temperature on one of the probes in storage tank 1 is

higher than the maximum permitted storage tank temperature

ID6001 HW request

There is an active requirement to charge the storage tank

ID6002 Heat pump compressor

start

Heat pump compressor start

ID6003 Switching cycle disa-

bled (I/O2)

The heat pump was disabled in order to reduce the compres-

sor's switching cycles

ID6005 Internal pump lead time

The internal pump runs at reduced speed during the pump lead

time

ID6006 Switching cycle disa-

bled

The heat pump was disabled in order to reduce the compres-

sor's switching cycles

ID6007 Min. holding time

The heat pump is disabled due to a minimum holding time

ID6008 Disable signal

S16

The heat pump is disabled due to a disable signal

ID6009 Disable signal (I/O 2)

The heat pump is disabled due to a disable signal

ID6010 Heat pump compressor

start (I/O 2)

Heat pump compressor start

ID6012 Defrosting HP (I/O 2)

Defrost heat pump

ID6020 Pump internal

after-run time

The internal pump runs at a reduced speed during the pump

after-run time

ID6103 Heat demand HP

Heat demand, heat pump

ID6104 Cooling demand HP

Cooling demand, heat pump

ID6105 Defrost heat pump

Defrost heat pump

ID6107 Standby mode enabled

Standby mode enabled

ID6108 Random delay after

power failure

Random delay after power failure (up to 200 seconds after

power returns) - the purpose of the random delay is to avoid a

system overload due to many consumers being switched on at

the same time

ID6109 Outdoor temp. Heat

pump usable limit

Outdoor temp. Heat pump usable limit - the heat pump is disa-

bled due to the usable limits being exceeded or not being

reached

ID6111 Heat pump bivalence

temperature

Heat pump bivalence temperature - the heat pump is disabled

because the temperature has dropped below the bivalence

temperature

ID6113 Solar heating

Solar heating - heat generators are disabled

ID6115 Low pressure differ-

ence

The pressure difference is too low to start the compressor

ID6116 Maximum defrosting

period

Maximum defrosting period