beautypg.com

Configuration…… 72, V - view configuration – Measurement Computing Digital488/80A User Manual

Page 78

background image

V - View Configuration

SYNTAX

Vval

View (but not load) configuration

val

, where

val =

value from

0

to

100

.

DESCRIPTION

The View Configuration (

V

) command is used to look at a configuration previously-saved without loading it for use as

the present configuration. In response to this command, the Digital488/80A returns a string in the following format:

S###C#F#G#I###K#M###P#R#Y#D0000000000Z

where each

#

equals the option for that command saved in

the requested configuration. Data between the

D

and the

Z

are dependent upon the state of the I/O lines at the time

when the configuration was saved.

EXAMPLE

PRINT#1,"CLEAR08"

Line 1: Reset the Digital488/80A.

PRINT#1,"OUTPUT08;V18X"

Line 2: View configuration 18.

INPUT#2,A$,

PRINT A$

Line 4: Display is:

S018C5F2G2I000K1M016P0R1Y2D0000000000Z

where this message is interpreted as follows:

S018

- Saved configuration 18.

C5

- All 5 ports are outputs.

F2

- ASCII binary data format.

G2

- Only output port data sent when addressed to Talk.

I000

- Data lines are active high.

K1

-

EOI

disabled.

M016

-

SRQ

on Ready.

P0

- All 5 ports are selected.

R1

- Data is latched on an EDR transition.

Y2

- Bus terminator is

CR

only.

D0000000000Z

- All I/O lines are active low.

72 Digital488/80A Commands

967695

Digital488/80A User's Manual