beautypg.com

Measurement Computing Digital488/80A User Manual

Page 77

background image

K#

End-Or-Identify

K0 EOI

enabled; assert

EOI

on last byte transferred.

K1 EOI

disabled; do not assert

EOI

on last byte transferred.

L####

Buffer

####

The number of port readings in the internal data buffer (from

0

to

2000

).

M##

Service Request Mask

M0 SRQ

is disabled.

M1 SRQ

on Service input transition.

M2 SRQ

on EDR input transition.

M4 SRQ

on IEEE 488 bus error.

M16 SRQ

on Ready.

Note:

The status message reflects the sum of all received Service Request Mask commands.

P#

Port Select

P0

All 5 ports selected.

P1

Port 1 selected.

P2

Port 2 selected.

P3

Port 3 selected.

P4

Port 4 selected.

P5

Port 5 selected.

R#

Data Ready

R0

Data is not latched, but is read whenever the Digital488/80A is addressd.

R1

Data is latched on an EDR transition.

R2

Data is latched and buffered on an EDR transition.

Y#

Bus Terminator

Y0

Carriage-return line-feed (

CR LF

).

Y1

Line-feed carriage-return (

LF CR

).

Y2

Carriage return (

CR

) only.

Y3

Line feed (

LF

) only.

Digital488/80A User’s Manual

967695

Digital488/80A Commands 71