beautypg.com

5 – operation – Greenheck AMD-xx-TD Transmitter User Manual

Page 9

background image

9

After 20 seconds, the display will return to Normal
display mode, and the dot in the upper right of the
display indicating CPU Activated will blink rapidly (4
times per second). This is Normal operation mode
and no further user interface is required. If, however,
user would like to verify configuration or change user
selectable parameters, continue to Section 5.4 entitled
“CONFIGURATION”.

5 – OPERATION

5.1 – INTRODUCTION

The Vari-Green has been configured at the factory to

customer specified parameters. Review this information

and verify that the Vari-Green set-up is correct for

your application. If any problems or discrepancies are

detected, contact Greenheck Dampers at 1-800-717-

6540 prior to proceeding.

5.2 – START-UP

1. After Installation has been verified in accordance with

Section 4, turn power switch located at the lower front
side to the ON position (see Figure 4.1).

2. Display will briefly indicate:
Followed by:

The number of active sensors will be represented by

the bar graph and listed below. There are 8 active
sensors in this example.

After 5 seconds, display will indicate:

The number of enabled sensors will be represented
by the bar graph and listed below. There are 8 active
sensors in this example.

After 5 seconds, display will indicate:
with the progressing from left to right.

Vari-Green

- - - - - - - - - - - - - - - - - - -

Thanks for Choosing

Greenheck

*

0 ACFM

VELO 0 AFPM
TEMP 68.0°F

1 8 16 24 32

Sensors Found: 8
Total Sensors: 8

1 8 16 24 32

Enabled Sensors: 8
Total Sensors: 8

Vari-Green

®

- - - - - - - - - - - - - - - - - - - -

Sensor Warming Up

Normal

display mode

* Dot flashes 4 times a second, indicating that
CPU is active. If ALERT flashes instead of Dot, see
section for Diagnostics.

5.3 - NORMAL OPERATION

Under Normal operation, the

Vari-Green transmitter will

continuously display flow and velocity, or temperature.

5.4 - CONFIGURATION

The Vari-Green onboard microprocessor controls
Configuration: Operating parameter selection; input/
output activation and scaling, and display scaling.
The customer can verify configuration and change
certain parameters (within defined ranges) by
entering the Vari-Green Configuration mode. This is
accomplished using the four membrane pushbuttons
located on the Vari-Green cover. See Figure 4.1 for
location of pushbuttons.