5.5 – PUSHBUTTON DEFINITION

The four pushbuttons used to interface with the

Vari-Green are as follows: UP DN ENT ESC

In addition to use during Configuration programming, pushbuttons can be used for certain functions when in the
Normal

operation mode. The following list describes the pushbutton function when in the Normal operation mode

and in the User Setup (programming).
When in Normal Operation Mode.
ENT then ESC then UP then ENT

Activates the Operator menu.

ENT then ESC then DN then ENT

Activates the Supervisor menu.

ENT

Activates Password selection menu.

ENT then UP then DN then ENT

Displays ID, ESID, and WO#. Press UP and software version and maximum
velocity will be displayed. Press ESC and the display will go back to the
Normal

operation mode.

When in User Setup.
UP or DN

Use to scroll to the desired Main Menu item.

Use to scroll to the value or mode within a parameter.

ENT

Enters user into specific selection sub-menu from Main Menu Selection.

Displays current setting of selected Parameter. Enters the selected value or
setting into memory.

ESC

Use as an escape key to exit back to Main Menu selection to avoid scrolling
to Return to MAIN MENU

The following pushbutton combinations can be used to more quickly set user selected values (i.e. Process Min and
Max Values, etc.).
UP* + ESC

Increases the second column digit.

DN* + ESC

Decreases the second column digit.

UP* + DN

Increases the third column digit.

XXXXX

DN* + UP

Decreases the third column digit.

UP* + ESC + DN

Increases the fourth column digit.

DN* + ESC + UP

Decreases the fourth column digit.

*Must be pressed and held before other button(s) are pressed.
Note: Pushbuttons are momentary type and should be quickly pressed and released to initiate desired change,

unless otherwise instructed to press and hold.

5.6 – CONFIGURATION PROGRAMMING

1. With power ON and initialization complete (see Section 5.2), press ENT then ESC then UP then ENT to activate

the Operator menu. The display will indicate:

Note: If Operator Menu password has been bypassed (see Section 5.7), the display will indicate as shown in Step 3

below.

2. Using UP and ENT, scroll to the numeric password for the Operator Menu. From the Factory, password is set for

1,111.

3. Once password is displayed, press ENT and display will indicate:

4. Press ENT and display will indicate:

By using UP and DN, the user can scroll through the following selections:

2nd Column
3rd Column
4th Column

ENTER PASSWORD FOR

OPERATOR MENU

XXXX

OPERATOR MENU

OPERATOR PASSWORD