Greenheck AMD-xx-TD Transmitter User Manual
Page 24

24
Flow Alarm
Configuration
Alarm 1 Off/On
Selection
Operator Menu
Alarm 1 Off/On
OFF
Alarm 2 Off/On
OFF
Alarm 1, Low Setpt
250 [units]
Alarm 2, High Setpt
250 [units]
Alarm 1 Dead Band
50 [units]
Alarm 2 Dead Band
50 [units]
Alarm Delay
0.0 Min.
Return to
MAIN MENU
Temp Alarm Configuration Menu
1
- Alarm 1 Off/On Selection
- Alarm 2 Off/On Selection
- Alarm 1 Setpoint Selection
- Alarm 2 Setpoint Selection
- Alarm 1 Dead Band Selection
- Alarm 2 Dead Band Selection
- Alarm Delay Selection
- Return to MAIN MENU
- Flow Alarm Configuration
Temperature Alarm Config
- OPERATOR MENU EXIT
¹ Available only with BAC net.
Default selection shown
Available selections
OFF or ON
OFF or ON
Depends on Temp
Units
Depends on Temp
Units
Depends on Temp
Units
Depends on Temp
Units
0.0 to 10.0 Min.
in 0.1 increments
1. While in Main Menu, use UP or DN to scroll to:
2. Press ENT to enter Alarm Configuration menu. Display will indicate:
3. Press ENT and display will indicate current setting of Alarm 1 (OFF or ON).
4. Use UP or DN to change setting. Once desired setting is displayed, press ENT. New setting will be stored in memory
and display will return to Alarm Configuration menu as in Step 2.
Note: If user desires not to change the setting and return to Alarm Configuration menu, press
ESC. Unit will remain
programmed as it was originally.
5. Use UP or DN to select remaining parameters to be changed.
6. Follow Step 4 to make any changes to parameters.
7. To return to Main Menu, select Return to MAIN MENU in Alarm Configuration menu and press ENT.