5.8 – FLOW CONFIGURATION
This Operator Menu selection is where all application specific data is entered to configure the Vari-Green for a
unique application. Typical data includes: Units of Measure, Duct Type and Size, Flow Type, Units and Conditions,
and Output Lockdown.
Note: The factory has entered data in this section based on customer supplied information. Data can be reviewed
and verified by scrolling through the individual menu items or reviewing the Factory Set-Up Information
sheet provided separately. Review this information BEFORE making any changes as it can have a
significant effect on the operation of the Vari-Green.
1. While in Operator Menu, use UP or DN to scroll to:
2. Press ENT to enter Flow Configuration menu. Display will indicate:
3. Press ENT and display will indicate current setting of Units (U.S. or METRIC).
Flow
Configuration
Dimensional Units
Selection
Operator Menu
Dimensional Units
U.S.
Temperature Units
°F
Duct Shape
RECTANGULAR
Duct Height
XX.XX in.
Duct Width
XX.XX in.
Duct Diameter
XX.XX in.
Duct Area
XX.XX Sq. Ft.
Actual or Standard
ACTUAL
Site Elevation
0 Feet
Volume Units
ACFM
Design Full Range
XX,XXX ACFM
Maximum Full Range
XX,XXX ACFM
4
Output Lockdown
200 AFPM
Return to
MAIN MENU
Flow Configuration Menu
Operator Menu
- Dimensional Units Selection
- Temperature Units Selection
- Duct Shape Selection
- Duct Height Selection ¹
- Duct Width Selection ¹
- Duct Diameter Selection ²
- Duct Area Selection ³
- Actual or Standard Selection
- Site Elevation Selection
- Volume Units Selection
- Design Full Range Selection
- Output Lockdown Selection
- Return to MAIN MENU
- Operator Password Selection
Flow Configuration
- Display Configuration
¹ Available only if RECT ANGULAR or OVAL is
selected as Shape
² Available only if ROUND is selected as Shape.
³ Available only if OTHER is selected as Shape.
Default slection shown
U.S or METRIC
°F or °C
RECTANGULAR, ROUND,
OVAL, FAN INLET-SINGLE,
FAN INLET-DOUBLE, or
OTHER
0.00 to 300.00 in.
0 to 10,000 mm
0.00 to 300.00 in.
0 to 10,000 mm
0.00 to 325.00 Sq.Ft.
0 to 35,500 Sq. M.
Actual or
Standard
0 to 15,000 Feet
0 to 4,572 M.
See UNITS list for
available
selections
Design value
adjustable up to
maximum value.
0 to 5000 AFPM
0.00 to 300.00 in.
0 to 10,000 mm
4
Maximum Full Range is based
on the duct area.