beautypg.com

Greenheck AMD-xx-TD Transmitter User Manual

Page 19

background image

19

Pushbutton

Combination

4-20mA

Output Type

0-5VDC

0-10VDC

UP only

+0.001mA

+0.3mV

+0.6mV

DN only

-0.001mA

-0.3mV

-0.6mV

UP* + ESC

+0.01mA

+0.003V

+0.006V

DN* + ESC

-0.01mA

-0.003V

-0.006V

UP* + DN

+0.1 mA

+0.03V

+0.06V

DN* + UP

-0.1mA

-0.03V

-0.06V

UP* + ESC* and DN

+1.0mA

+0.3V

+0.6V

DN* + ESC* and UP

-1.0mA

-0.3V

-0.6V

*Must be pressed and held before other button(s) are pressed.

6. Once an acceptable zero reading is obtained, press ENT and then UP and display will indicate:

7. Press ENT. Display will indicate:

8. With DMM still connected as in Step 4, reading should be at maximum value; 10.00 ± 0.01 volts, 5.00 ± 0.01 volts,

or 20.00 ± 0.1mA.

9. If DMM is reading out of tolerance, use UP or DN to adjust the Vari-Green’s output for an acceptable DMM

reading.

10. Once an acceptable span reading is obtained, press ENT and then UP and display will indicate:

11. Repeat Steps 3 through 10 for Transmitter Output 2. For Transmitter Output 2, connect DMM across terminals 3

and 4.

12. Press UP and display indicates:

Output 1 Span

Selection

Type is 4-20 mA

Output 1 Span

Selection

Type is 4-20 mA

Output 1 Zero

Selection

Type is 4-20 mA

Return to

MAIN MENU