17

5.11 – Low Pass Filter

Allows selection of level of Process filtering applied to the output. Levels are 0 to 10, with 0 representing no filtering
and 10 representing maximum filtering. Display Filter is an additional filter selection applied only to the display.
This filtering affects all subsequent outputs and displays.

1. While in Operator Menu, use UP or DN to scroll to:

2. Press ENT and display will indicate current setting of Process filter; (0 (none) to 10

(maximum).

3. Use UP or DN to change setting. Once desired setting is displayed, press ENT. New setting will be stored in

memory and display will return as in Step 1.

Note: If user desires not to change the setting and return to Output 2 Parameter menu, press

ESC. Unit will

remain programmed as it was originally.

Low Pass Filter

1 (Minimum)

0 (None) to

10 (Maximum)

Operator Menu

Default selection shown

Available selections

- Output 2 Parameter Selection

Low Pass Filter Selection

- Output Signal Type Selection

Low Pass Filter

Selection

5.12 – Output Signal Type Selection

User can select signal type for Output 1 and 2.
The output types selected below must correspond to the types selected via jumpers J3 through J7 (see Section 4.5).

1. While in Main Menu, use UP or DN to scroll to:

2. Press ENT to enter Output Signal Type menu. Display will indicate:

3. Press ENT and display will indicate current signal type (4-20mA).
4. Use UP or DN to change signal type. Once desired signal type is displayed, press ENT. New signal type will be

stored in memory and display will return to Output Signal Type Selection menu as in Step 2.

Note: If user desired not to change the signal type and return to Output Signal Type Selection menu, press ESC.
Unit will remain programmed as it was originally.

5. Use UP or DN to select remaining parameters to be changed.
6. Follow Step 4 to make any changes to parameters.
7. To return to Main Menu, select Return to MAIN MENU in Output Signal Type Selection menu and press ENT.

- Output 1 Signal Type Selection

- Output 2 Signal Type Selection

- Return to MAIN MENU

Output 1 Signal Type

4-20 mA

Return to

MAIN MENU

Output 2 Signal Type

4-20 mA

4-20 mA,

0-10 Vdc, 0-5 Vdc

4-20 mA,

0-10 Vdc, 0-5 Vdc

- Low Pass Filter Selection

Output Signal Type Select

- Transmitter Output Calibration

Operator Menu

Output Signal Menu

Default selection shown

Available selections

Output Signal Type

Selection

Output Signal Type

Selection