17 – flow alarm configuration, 16 – network configuration – Greenheck AMD-xx-TD Transmitter User Manual
Page 22

22
1. While in Main Menu, use UP or DN to scroll to:
2. Press ENT to enter Network Configuration menu. Display will indicate:
3. Press ENT and display will indicate current setting of Network (OFF or ON).
4. Use UP or DN to change setting. Once desired setting is displayed, press ENT and new setting will be stored in
memory and display will return to Network Configuration menu as in Step 2.
Note: If user desires not to change the setting and return to Network Configuration menu, press
ESC. Unit will
remain programmed as it was originally.
5. Use UP or DN to select remaining parameters to be changed.
6. Follow Step 4 to make any changes to parameters.
7. To return to Main Menu, select Return to MAIN MENU in Network Configuration menu and press ENT.
5.17 – Flow Alarm Configuration
Available only with BACnet Network option.
User can turn each Alarm ON or OFF, select type of alarm and set the following values:
Alarm 1 Setpoint (this is Low, Low1, or High1 depending on Alarm Type): Selected value of flow below (for Low and
Low1) or above (for High 1) which an alarm condition will exist.
Alarm 2 Setpoint (this is High, Low2, or High2, depending on Alarm Type): Selected value of flow below (for Low2) or
above (for High and High2) which an alarm condition will exist.
Alarm Deadband: Value that transmitter signal has to reach above (for Low, Low1, or Low2) or below (for High, High1,
or High2) before an activated alarm will reset. Value is selected in same units as transmitter span.
Alarm Delay: Time between an alarm condition existing and alarm activation. Adjustable between 0.0 and 10.0 minutes
in 0.1 minute increments.
Network
Configuration
Network Off/On
Selection
5.16 – Network Configuration
Allows user to turn network ON or OFF, and configure parameters based on Network type. BACnet available only with
version 1.5X.
Operator Menu
Network Off/On
OFF
BACnet Instance ID
0
BACnet Address
1
BACnet Max Masters
1
Bacnet Baud Rate
9600
Network Configuration Menu
1
- Network ON/OFF Selection
- BACnet Instance ID Selection
2
- BACnet Instance ID Selection
2
- BACnet MaxMasters Selection
2
- BACnet Baud RateSeleciton
2
- Return to MAIN MENU
- Menu Inactivity Timeout Select
Network Configuration
- Flow Alarm Configuration
¹ Available only with Network option
² Available only with BACnet
Default slection shown
OFF or ON
0 to 4,194,303
1 to 127
1 to 127
9600, 19200,
38400, or 76800
Return to