5.14 – K-Factor Configuration

Caution

In the majority of applications, the use of a K-Factor is neither required nor desirable.

Before using the K-Factor feature, contact the factory (see Section 8) to review

the application and obtain assistance in determining the K-Factor exponent and gain values.

Turns K-factor function ON or OFF, calculate a K-Factor exponent and gain from measured data, or select a K-Factor
exponent value and K-Factor gain value.

Note: If K-Factor is ON, Process displays will have an asterisk (KFon) to the right of the flow value.

Operator Menu

K-Factor Off/On

OFF

Calculate K-Factor?

NO

Numbr of Data Points

One Point

Measured Point 1

1,000 ACFM

Measured Point 2

5,000 ACFM

Measured Point 3

9,000 ACFM

Reference Point 1

1,000 ACFM

Reference Point 2

5,000 ACFM

Reference Point 3

9,000 ACFM

EXPO: 1.0000

GAIN: 1.000

K-Factor Exponent

1.0000

K-Factor Gain

1.000

Return to

MAIN MENU

Flow Configuration Menu

Operator Menu

- K - Factor Off/On Selection

- Calculate K-Factor? Selection

- Numbr of Data Points Selection

1

- Measured Point 1 Selection ¹

- Measured Point 2 Seleciton ¹

,2

- Measured Point 3 Selection

1,

²

- Reference Point 1 Selection

1

- Reference Point 2 Selection

1,2

- Reference Point 3 Selection

1,2

- Perform Calculation Selection

1

- K-Factor Exponent Selection

3

- K-Factor Gain Selection

3

- Return to MAIN MENU

- Transmitter Output Calibration

K-Factor Configuration

- Menu Inactivity Timeout Select

¹ Available only if YES is selected in Calculate K-Factor?

² Depends on the number of Data Points selected

³ Available only if NO is selected in Calculate K-Factor?

Default slection shown

OFF or ON

NO or YES

One Point

Two Points

Three Points

Uses Process Units

& Format Selected

in Process Config.

Calulated from data

entered above

0.5000 to 2.0000*

0.0001 increments

0.000 to 32.750*

0.0001 increments

*Available Range depends on

operating span versus natural

span.

Uses Process Units

& Format Selected

in Process Config.

Uses Process Units

& Format Selected

in Process Config.

Uses Process Units

& Format Selected

in Process Config.

Uses Process Units

& Format Selected

in Process Config.

Uses Process Units

& Format Selected

in Process Config.