5.14 – K-Factor Configuration
Caution
In the majority of applications, the use of a K-Factor is neither required nor desirable.
Before using the K-Factor feature, contact the factory (see Section 8) to review
the application and obtain assistance in determining the K-Factor exponent and gain values.
Turns K-factor function ON or OFF, calculate a K-Factor exponent and gain from measured data, or select a K-Factor
exponent value and K-Factor gain value.
Note: If K-Factor is ON, Process displays will have an asterisk (KFon) to the right of the flow value.
Operator Menu
K-Factor Off/On
OFF
Calculate K-Factor?
NO
Numbr of Data Points
One Point
Measured Point 1
1,000 ACFM
Measured Point 2
5,000 ACFM
Measured Point 3
9,000 ACFM
Reference Point 1
1,000 ACFM
Reference Point 2
5,000 ACFM
Reference Point 3
9,000 ACFM
EXPO: 1.0000
GAIN: 1.000
K-Factor Exponent
1.0000
K-Factor Gain
1.000
Return to
MAIN MENU
Flow Configuration Menu
Operator Menu
- K - Factor Off/On Selection
- Calculate K-Factor? Selection
- Numbr of Data Points Selection
1
- Measured Point 1 Selection ¹
- Measured Point 2 Seleciton ¹
,2
- Measured Point 3 Selection
1,
²
- Reference Point 1 Selection
1
- Reference Point 2 Selection
1,2
- Reference Point 3 Selection
1,2
- Perform Calculation Selection
1
- K-Factor Exponent Selection
3
- K-Factor Gain Selection
3
- Return to MAIN MENU
- Transmitter Output Calibration
K-Factor Configuration
- Menu Inactivity Timeout Select
¹ Available only if YES is selected in Calculate K-Factor?
² Depends on the number of Data Points selected
³ Available only if NO is selected in Calculate K-Factor?
Default slection shown
OFF or ON
NO or YES
One Point
Two Points
Three Points
Uses Process Units
& Format Selected
in Process Config.
Calulated from data
entered above
0.5000 to 2.0000*
0.0001 increments
0.000 to 32.750*
0.0001 increments
*Available Range depends on
operating span versus natural
span.
Uses Process Units
& Format Selected
in Process Config.
Uses Process Units
& Format Selected
in Process Config.
Uses Process Units
& Format Selected
in Process Config.
Uses Process Units
& Format Selected
in Process Config.
Uses Process Units
& Format Selected
in Process Config.