18 – temperature alarm configuration, 17 – flow alarm configuration (cont.) – Greenheck AMD-xx-TD Transmitter User Manual
Page 23

23
1. While in Main Menu, use UP or DN to scroll to:
2. Press ENT to enter Alarm Configuration menu. Display will indicate:
3. Press ENT and display will indicate current setting of Alarm 1 (OFF or ON).
4. Use UP or DN to change setting. Once desired setting is displayed, press ENT. New setting will be stored in memory
and display will return to Alarm Configuration menu as in Step 2.
Note: If user desires not to change the setting and return to Alarm Configuration menu, press
ESC. Unit will remain
programmed as it was originally.
5. Use UP or DN to select remaining parameters to be changed.
6. Follow Step 4 to make any changes to parameters.
7. To return to Main Menu, select Return to MAIN MENU in Alarm Configuration menu and press ENT.
5.18 – Temperature Alarm Configuration
Available only with BACnet Network option.
User can turn each Alarm ON or OFF, select type of alarm and set the following values:
Alarm 1 Setpoint (this is Low, Low1, or High1 depending on Alarm Type): Selected value of temperature below (for
Low and Low1) or above (for High 1) which an alarm condition will exist.
Alarm 2 Setpoint (this is High, Low2, or High2, depending on Alarm Type): Selected value of temperature below (for
Low2) or above (for High and High2) which an alarm condition will exist.
Alarm Deadband: Value that transmitter signal has to reach above (for Low, Low1, or Low2) or below (for High, High1,
or High2) before an activated alarm will reset. Value is selected in same units as transmitter span.
Alarm Delay: Time between an alarm condition existing and alarm activation. Adjustable between 0.0 and 10.0 minutes
in 0.1 minute increments.
5.17 – Flow Alarm Configuration (cont.)
Operator Menu
Alarm 1 Off/On
OFF
Alarm 2 Off/On
OFF
Alarm 1, Low Setpt
250 [units]
Alarm 2, High Setpt
250 [units]
Alarm 1 Dead Band
50 [units]
Alarm 2 Dead Band
50 [units]
Alarm Delay
0.0 Min.
Return to
MAIN MENU
Flow Alarm Configuration Menu
1
- Alarm 1 Off/On Selection
- Alarm 2 Off/On Selection
- Alarm 1 Setpoint Selection
- Alarm 2 Setpoint Selection
- Alarm 1 Dead Band Selection
- Alarm 2 Dead Band Selection
- Alarm Delay Selection
- Return to MAIN MENU
- Network Configuration
Flow Alarm Configuration
- Temperature Alarm Config
¹ Available only with BAC net.
Default selection shown
Available selections
OFF or ON
OFF or ON
Depends on Flow
Units
Depends on Flow
Units
Depends on Flow
Units
Depends on Flow
Units
0.0 to 10.0 Min.
in 0.1 increments
Flow Alarm
Configuration
Alarm 1 Off/On
Selection