6 - supervisor menu – Greenheck AMD-xx-TD Transmitter User Manual
Page 25

25
6 - Supervisor Menu
6.1 – Introduction
The Supervisor menu allows individual sensors to be enabled or disabled, scan all sensors for status, and perform
diagnostics on any alert conditions.
1. To enter the Supervisor Menu, press ENT then ESC then DN then ENT at the same time.
The display will indicate:
Note: If Supervisor Menu password has been bypassed, display will indicate as shown in Step 3 below.
2. Using UP or DN scroll to the numeric password for the Supervisor Menu. From the Factory, password is set to
2,222.
3. Once password is displayed, press ENT, and the display will indicate:
4. Press ENT, and the display will indicate:
By using UP or DN, supervisor can scroll through the following selections.
ENTER PASSWORD FOR
SUPERVISOR MENU
XXXXX
SUPERVISOR MENU
SUPERVISOR PASSWORD
SELECTION
MENU SELECTION
DESCRIPTION
Supervisor Password Selection
Allows for the selection of password for the Supervisor menu, and
the option to bypass the password.
Sensor Management
Allows for the scanning of the sensor network for active and/or
enabled sensors. Also allows for the enabling/disabling of individual
sensors.
Diagnostic Display Selection
Displays each sensor’s current reading of velocity and temperature
Diagnostic ALERT Determination
Displays any sensor or average that currently has an ALERT
condition and the ALERT code.
Power Cycle Sensor Network
Allows for the cycling of power to the sensors.
Supervisor Menu Exit
Returns display to Normal operation.
Once the desired selection is displayed, press ENT to enter its sub-menu.