B outputs 9 ~ 16 – AGI Security GV-CONCT User Manual
Page 57

GV-AS400 Controller
47
3
To connect an output device:
Connect the (+) point on the output device to COM on GV-AS400, connect the two (-) points
of the output device and the external power supply together, and connect the (+) point on the
external power supply to the NO or NC of GV-AS400 based on the state of the output device.
Figure 3-6
3.2.3.B Outputs 9 ~ 16
Outputs 9 ~ 16 only accept the power from GV-AS400 circuit board. Check if your output
device meets the following absolute maximum ratings before connecting it to any of outputs
9 ~ 16.
Breakdown Voltage
350V DC / AC
Continuous Load Current
130mA
Power Dissipation
500mW
Note: Absolute Maximum Ratings are those values beyond which damage to GV-AS400
circuit board may occur. Continuous operation of GV-AS400 at the absolute rating level may
affect GV-AS400 reliability.
WANRING: Do not connect any external power supply to outputs 9 ~ 16; otherwise damage
to GV-AS400 circuit board may occur.