AGI Security GV-CONCT User Manual
Page 143
Optional Devices
133
4
[Events]
Set the parameters for the events.
Figure 4-43
•
When Door Entry/Exit Control or Parking Entry/Exit Control is selected in the
Function Setting page (Figure 4-41), these options become available:
Option
Description
Anti-Passback
Enables or disables the Anti-Passback function. The option is only
available for Door/Gate A.
Gate Open Time
Sets the time (1 to 255 sec.) that a parking gate remains open after
which the gate will automatically be locked. The option is only
available when Parking Entry/Exit Control is selected.
Lock Reset Time
Sets the time (1 to 255 sec.) that a door remains open after which
the door will automatically be locked. The option is only available
when Door Entry/Exit Control is selected.
Held Open Time
Sets the time (5 to 9999 sec.) that a door/gate can be held open
before an alarm is generated.
Fire Action
Locks or unlocks the door/gate when a fire condition occurs.
Otherwise, remains the door’s current state by selecting
Unchanged.
Alarm Continuous
Time
Sets the time (1 to 10 sec.) that the alarm will continuously go off
before it ends.
•
When Elevator Control is selected in the Function Setting page (Figure 4-41), these
options become available:
Option
Description
Relay on Time
Sets the time (1 to 255 sec.) that an elevator door remains open
after which the door will automatically be closed.
Fire Action
Alarm Continuous
Time
See the same option above.