2 pssu system in the automation system pss 4000, 4application example, 3 device configuration – Pilz PNOZ mmc1p ETH User Manual

Page 42

background image

4.3

Device configuration

4

Application example

Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: [email protected]

4-6

Base unit PNOZ mm0.1p

1. Base unit PNOZ mm0.1p

2. Configure communication module PNOZ mmc1p ETH

3. Insert inputs/outputs that are downloaded via the integrated interface

4.3.2

PSSu system in the automation system PSS 4000

PSSu system in the automation system PSS 4000

4-

ModbusTCP_Bsp_Konfiguration-PSS 4000

The configuration is made in PAS4000.

Create IP connection

Create the IP connection in the IP Connections Editor

1. Enter remote IP address

>

Enter the IP addresses of the PNOZmulti Ethernet connections.

2. Enter remote port number

>

Enter the port number "502".

The number may not be modified.

3. Select function code

>

From the list, select "WriteMultipleCols0x"

4. Define the start address and the length of the data block

>

Enter the start address and the data length in the "Send" field