Assignment of data areas

3

Modbus/TCP - Data areas

3.4.2

Control Register

Control Register

3-

ModbusTCP_Datenbereiche-Control Register-PNOZmulti

A watchdog can be activated in Control Register 255.

If no input bits are set by a Modbus/TCP subscriber within the preset

time, the PNOZmulti will set the input bits to "0".

The table below describes the Modbus/TCP data areas for the watch-

dog.

A relevant area for the watchdog is defined in each Modbus/TCP data

area (Coils (0x), Discrete Inputs (1x), Input Register (3x), Holding Register

(4x)). Read/write access will depend on the Modbus/TCP data area.

Bit 15 "Watchdog Trigger": The watchdog can be triggered by setting Bit

15 constantly to "1", or by a Client writing in the input area of the 128

inputs. The state of the bit when reading is undefined. A 1 or a 0 can be

read.

Bit 14 "Error Message": If this bit is set, an error stack entry is generated

when the watchdog is triggered.

Bit 10 … 8 "WD Timer": If the set time for the watchdog is set, then Bit

15 must be set, or become set, at the same time.

Register
(3x, 4x)

Coil/
Discrete Input
(0x, 1x)

Content

High Byte

Low Byte

255

4095...4080

Control Register

See table below

High Byte

WD-Trig-
ger

Error Mes-
sage

Reserved

Reserved

Reserved

W-Timer
Bit 2

W-Timer
Bit 1

W-Timer
Bit 0

Low Byte

Reserved

Reserved

Reserved

Reserved

Reserved

Reserved

Reserved

Reserved

Watchdog Timer Bit 2

Watchdog Timer Bit 1

Watchdog Timer Bit 0

Watchdog time

0

0

0

Timer deactivated

0

0

1

100 ms

0

1

0

200 ms

0

1

1

500 ms

1

0

0

1 s

1

0

1

3 s

1

1

0

5 s

1

1

1

10 s