Updating the data areas, 3modbus/tcp - data areas, 5 updating the data areas – Pilz PNOZ mmc1p ETH User Manual
Page 34
3.5
Updating the data areas
3
Modbus/TCP - Data areas
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: [email protected]
3-24
3.5
Updating the data areas
3500
Updating the data areas
3-
ModbusTCP_Aktualisierung der Datenbereiche-PNOZmulti
Data is updated with varying priority.
The table below shows the typical update cycles for the various data.
Content
Typ. update cycle
Virtual inputs/outputs
20 ms
Configuration
Once during initialisation
State of the inputs/outputs from the base unit and expansion modules
320 ms
LED status
1000 ms
Number of elements that can store a state
Once during initialisation
Element enable
320 ms
Diagnostic words
1000 ms
Element types
Once during initialisation
Current state of the virtual inputs
1000 ms
INFORMATION
The update time may increase if there are additional TCP/IP con-
nections (e.g. PNOZmulti Configurator, PMI, control system) on
the PG port (Port 9000).