3.5

Updating the data areas

3

Modbus/TCP - Data areas

Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: [email protected]

3-24

3.5

Updating the data areas

3500

Updating the data areas

3-

ModbusTCP_Aktualisierung der Datenbereiche-PNOZmulti

Data is updated with varying priority.

The table below shows the typical update cycles for the various data.

Content

Typ. update cycle

Virtual inputs/outputs

20 ms

Configuration

Once during initialisation

State of the inputs/outputs from the base unit and expansion modules

320 ms

LED status

1000 ms

Number of elements that can store a state

Once during initialisation

Element enable

320 ms

Diagnostic words

1000 ms

Element types

Once during initialisation

Current state of the virtual inputs

1000 ms

INFORMATION

The update time may increase if there are additional TCP/IP con-

nections (e.g. PNOZmulti Configurator, PMI, control system) on

the PG port (Port 9000).