beautypg.com

3modbus/tcp - data areas, 4 assignment of data areas – Pilz PNOZ mmc1p ETH User Manual

Page 30

background image

3.4

Assignment of data areas

3

Modbus/TCP - Data areas

Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: [email protected]

3-20

Register 938 to 944 "Element enable 1 ... 100"

Each element is assigned an ID in the PNOZmulti Configurator. If the el-

ement's output = 0 (no enable), the corresponding bit is set.

Register 1071 to 1126 "Element type"

The available element types are listed below.

1118

17903... 17888

Element type

Element ID = 90

Element ID = 89

1119

17919... 17904

Element type

0

Element ID = 91

1120

17935... 17920

Element type

Element ID = 93

Element ID = 92

1121

17951... 17936

Element type

Element ID = 95

Element ID = 94

1122

17967... 17952

Element type

Element ID = 97

Element ID = 96

1123

17983... 17968

Element type

Element ID = 99

Element ID = 98

1124

17999... 17984

Element type

Reserved

Element ID = 100

1125

18015... 18000

Element type

Reserved

Reserved

1126

18031... 18016

Element type

Reserved

Reserved

Byte 0

8

7

6

5

4

3

2

1

Byte 1

16

15

14

13

12

11

10

9

Byte 2

24

23

22

21

20

19

18

17

...

Byte 10

88

87

86

85

84

83

82

81

Byte 11

96

95

94

93

92

91

90

89

Byte 12

-

-

-

-

100

99

98

97

Element type
(Byte)

Element

Function elements

01

Switch type 1: N/C contact

02

Switch type 1: N/C contact, monitored reset

03

Switch type 1: N/C contact, manual reset

04

Switch type 1: N/C contact, start-up test

05

Switch type 1: N/C contact, start-up test, monitored reset

06

Switch type 1: N/C contact, start-up test, manual reset

Register
(3x)

Coil/
Discrete Input
(1x)

Content

High Byte