Page 10

background image

2.2

Modbus/TCP with PNOZmulti

2

Communication via Modbus/TCP

Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: [email protected]

2-2

2.2

Modbus/TCP with PNOZmulti

2200

Modbus/TCP with PNOZmulti

2-

ModbusTCP_Modbus/TCP Allg-2-PNOZmulti

All base units from the modular safety system PNOZmulti that have an

Ethernet interface (PNOZ m1p ETH from V2.1) support Modbus/TCP.

The same applies for the base units PNOZmulti Mini in conjunction with

a communication module with Ethernet interface.

A PNOZmulti base unit can manage a max. of 8 Modbus/TCP connec-

tions. The PNOZmulti is always the Server in a connection. The Clients

in the connections may be various devices, e.g. PC (PNOZmulti Config-

urator), control system, display unit. They can access the modular safety

system PNOZmulti simultaneously.

The virtual I/Os plus all the information that is polled during fieldbus

communication are contained in data areas. The data is accessed di-

rectly. It's no longer necessary to switch via table/segment.

The configurations required for Modbus/TCP are fully pre-configured in

the PNOZmulti operating system. All that's necessary in the PNOZmulti

Configurator is to activate the virtual inputs and outputs (see PNOZmulti

Configurator's online help, under "Display and edit module selection").

On a modular control system PNOZmulti, port number "502" is fixed as

the default for data exchange via a Modbus/TCP connection. It is not

displayed in the PNOZmulti Configurator and cannot be modified.